Filters Specifications
     

Installation Instructions

 

Click above

for

installation

instructions 
   
Model FST-634NS
Filter
Vessel
FST-RF6NS
Replaceable
Filter
Cartridge

 
FST-634 Installation Kit

 


FST-124 Installation Kit

FST-124 NS Filter Vessel
 RFA-NS-4 Replaceable Filter Cartridge
 Type  Use RF6
 Filter/trap coalescer  Filter/trap coalescer Cartridge

 Number of Cartridges Required

 1 FST-RF6 NA RFF-4 NA
In/Out Port Size  1 inch  1 inch 2 inch NPT, 1.5 inch NPT or 1 inch NPT NA
 Length  6 inches  4 inches 12-25 inches 5 inches
Diameter  5 inches  3 inches 7.5 inches  3 inches
 Flow rate  35 GPM*  35 GPM* 65 to 85 GPM*  NA
Life Span  NA  250,000 Gals** NA 500,000 Gallons**
Micron Filtration Stage Levels  NA  40 Micron Down to  5 Micron NA  40 Micron down to 5 Micron
 Efficiency Level  NA  99.5% NA 99.5%
Working Pressure  350 PSI  NA 350 PSI NA
Mounting  Vertical Use   Vertical Use Vertical Use Vertical Use
 Relief Valve  Hydrostatic  NA Hydrostatic   NA
Drain & Vent ports  1/4 inch bottom 1/4 inch top   1/4 inch bottom, 1/4 inch top   NA
*Recommended flow rates are for maximum efficiency      
**Fuel quality is governed by time of year, availability of product, and condition of storage tanks.      
***Adopt a workable maintenance program to insure maximum efficiency, equipment performance, and reduced emissions.

 

 

 

 

 

 

         
Model  FST-26
Disposable
Filter
Vessel
 FST-818 Dual Filter Vessel  FST-418 Single Filter Vessel Rff-8 HV 
         Filter/trap coalescer
Number of Cartridges Required  NA  2 RF-8  1 RF-8  NA
In/Out Port Size   3/8 inch NPT  3 inch*  3 inch*  
         125 GPM*
Life Span   1,000 Gals**  NA  NA  800,000 to 1,200,000 gallons**
Micron Filtration Stage Levels   40 Micron Down to  5 Micron  NA  NA  40 micron down to 5 micron
Efficiency Level    99.5%  NA  NA  99.5%
Working Pressure   150 PSI  350 PSI  350 PSI  350 PSI
Mounting    Vertical or Horizontal Use  Vertical Use  Vertical Use NA
Relief Valve  NA  Hydrostatic  Hydrostatic  NA
Drain & Vent ports  NA  1/4 NPT  1/4 NPT NA
 *Recommended flow rates are for maximum efficiency
**Fuel quality is governed by time of year, availability of product, and condition of storage tanks.  
***Adopt a workable maintenance program to insure maximum efficiency, equipment performance, and reduced emissions.